Peak shaving is an energy management technique where you reduce or "shave off" the highest peaks in electricity consumption to avoid expensive power peaks. For many companies, it is precisely these short periods of very high load that can have a disproportionate impact on grid fees and capacity charges. With smart meters and modern management, peak shaving is now a practical option – often through a combination of consumption management and local energy supply such as batteries. Here we review what peak shaving is, when it makes sense, how it is implemented, and what trade-offs you need to be aware of before you decide.
Definition: Peak shaving (also known as peak load shaving or load shedding) involves reducing the highest peaks in electricity consumption during short periods. In practice, you even out the load so that your maximum power draw from the grid is lower.
The reason for this is that the electricity grid is dimensioned according to maximum consumption – even though peak loads occur only rarely. That is why many tariffs include elements where the price depends wholly or partly on your highest measured load during a period, often measured in 15-minute intervals. This means that even a short peak can have a financial impact far beyond the actual "peak minutes."
From an operational perspective, peak shaving is primarily a matter of control: you set an upper limit for power consumption and plan how to stay below that limit when multiple loads occur simultaneously. This can be a simple "stop block" on consumption or a more finely tuned control system, where selected loads are regulated in order of priority.
Peak shaving has become more relevant in Denmark with the spread of smart meters, which enable time-dependent tariffs (Time-of-Use/ToU). Five to six network companies have introduced ToU tariffs, which together cover an estimated 80% of Danish households.
Typical peak window: Many tariffs have a clear peak in the afternoon and evening hours – often between 5 and 8 p.m. – especially in the winter months (October to March). The price ratio between peak and off-peak varies between network companies and can, for example, be 0.01 DKK/kWh in off-peak versus 0.04 DKK/kWh in peak (ratio 4).
To assess the relevance in your case, you should first get an overview of what actually triggers extra costs in your tariff: Is it the energy (kWh at certain times), or is it the highest measured power in an interval? The two mechanisms may require different measures. Many therefore start by comparing hourly and quarter-hourly data fromthe meter/EMS with the operation's "known peaks" (e.g., production, ventilation, charging) so that you can see whether the peak is a recurring pattern or a rare event.
For private households, the relevance in Denmark remains more limited than for businesses, because capacity charges for households have not yet been widely introduced. However, in some EU countries, there is a trend towards capacity tariffs based on the highest 15-minute consumption, which may increase interest in peak shaving among private households over time.
Peak shaving primarily addresses costs resulting from your maximum power consumption. When capacity charges or demand charges are calculated based on the highest measured load (typically in 15-minute windows), a single peak can affect costs over a longer period (depending on your tariff model).
The key point is that peak power consumption often occurs as a combination of several loads occurring simultaneously. Therefore, it rarely makes sense to focus solely on the "big culprit." Instead, you should identify:
Once you know the "recipe" for peak demand, you can typically choose between avoiding simultaneity (planning/control) or supplying part of the peak locally (battery or other onsite source).
A concrete example from Germany illustrates the mechanism: A company with a constant load of 4,000 kW pays approximately €200,000 annually in grid fees. If the company receives a one-off order that requires +500 kW for just 30 minutes, the maximum increases to 4,500 kW, triggering approximately €25,000 in additional annual costs solely due to the short peak.
Demand-side peak shaving means reducing actual electricity consumption during peak periods. This can be achieved, for example, by avoiding the simultaneous operation of several energy-intensive processes or by temporarily throttling non-critical loads. In practice, this involves defining what needs to be regulated, for how long, and within what limits, so that operations and quality are not compromised.
Before making any changes to operations, it is beneficial to agree on a simple prioritization: Which loads are critical, which are flexible, and which can be turned off or reduced temporarily? Once the prioritization is in place, implementation typically becomes more robust because management has clear "rules of the game."
Examples of demand-side measures include:
What these measures have in common is that they should be explainable and testable in small steps. Start, for example, with a conservative effect limit and a short adjustment period so that you can verify that comfort, process stability, and product quality are not affected. Once you have documented what works in your everyday operations, you can adjust limits and automation.
An energy management system (EMS) can automate this by setting load limits and regulating when you approach a set threshold. EMS can use historical data, forecasts (e.g., for renewable production), and real-time measurements to predict peaks and manage proactively. To achieve a stable solution, thresholds, priorities, and fallback behavior should be clearly defined so that the system does not regulate more than necessary.
Supply-side peak shaving means that you cover peak loads with local power instead of drawing everything from the grid. This typically involves battery energy storage systems (BESS), solar cells in combination with storage, or on-site generators. This approach is relevant when peak loads are difficult to avoid through planning alone, or when you want a solution that can respond quickly to unforeseen loads.
Battery for peak shaving: The battery is charged during periods of low load or high local production (e.g., midday) and discharged during peak load to reduce power draw from the grid. Lithium-ion batteries—especially LiFePO4—have become standard in industrial and commercial applications with high cycle counts (3,000–5,000+), long life, and minimal maintenance.
In practice, you need to decide how the battery should "behave": Should it primarily be ready to handle short peaks, or should it be used more actively in everyday life? The more actively the battery is used, the more important it becomes to have clear limits for minimum charge status and prioritization, so that there is always capacity for the peak you want to protect yourself against.
Solar cells + battery: This combination may be relevant, even though solar production does not necessarily coincide with the typical peak between 5 and 8 p.m. Therefore, the interaction between control, storage, and load profile is key. A practical approach is to map out when you typically have high load and when you typically have local production, so that the control system can charge at the "right" times and relieve the grid when the peak actually occurs.
Practical peak shaving often requires continuous measurement and control of power consumption. Peak load monitors can track consumption continuously and operate at 15-minute intervals. If the system predicts that you will exceed a threshold in the next interval, it can automatically activate reduction of selected loads or relieve the load with battery power.
To get value from monitoring, you should clarify two things in advance: (1) what threshold triggers action, and (2) what actions may be used and in what order. A typical "control ladder" could be that the system first attempts soft measures (e.g., short-term regulation), and only if that is not enough, more intrusive measures are activated. This way, you avoid unnecessary impact on operations and comfort, while still protecting yourself against peak power consumption.
With DC fast charging, peaks can be short but expensive in a tariff model with capacity charges. This is because the power can rise rapidly when several cars are charging at the same time, and grid connection and charges can be sensitive to precisely the highest measured peak.
An example shows that a 350 kW charger can be fully utilized for an average of approximately 11 minutes per day, but the grid must still be dimensioned for peak demand. With intelligent peak shaving, the power supplied per charger can be reduced (e.g., to 100 kW), thereby lowering the overall demand. In a calculated example, this reduced the required power demand from 300 kW to 200 kW and lowered annual grid fees by about one-third. Another example shows a reduction in maximum simultaneous load from approx. 600 kW to approx. 400 kW and a reduction of more than 30% in annual fee costs.
The practical question is often where to draw the line: How much can you limit concurrency without compromising the user experience or your operational goals? Therefore, you should establish a strategy for when limitation is acceptable (e.g., for short periods) and how it is communicated and handled in operations. When the limits are clear, control can be implemented more consistently.
Peak shaving reduces the peak itself (the maximum load). Load shifting moves consumption to other times, typically from expensive hours to cheaper hours, without reducing the total kWh consumption.
Peak shaving is particularly relevant when:
If you are unsure about what to prioritize first, the rule of thumb is that load shifting often starts with planning and routines, while peak shaving typically requires a clear power limit and a mechanism that can "hold the line" when the load increases. In practice, the combination can have the greatest effect: shift flexible loads (load shifting) and reduce inflexible peak loads (peak shaving) with control and/or batteries.
Peak shaving is rarely "free" to operate. The more consistently you want to reduce peaks, the more important it is to clarify risks, responsibilities, and frameworks before the solution is put into operation. This applies to both demand-side management and battery-based peak shaving.
A robust way to handle trade-offs is to work with clear acceptance criteria: Which loads can be regulated, which cannot, how long can a regulation last, and what should the system do if data is incomplete or if operations change? When these parameters are decided in advance, peak shaving typically becomes more stable and easier to operate over time.